| Sign In | Join Free | My uabig.com |
|
Place of Origin : China
Brand Name : Kingsine
Model Number : K3040
Certification : ISO9001,CE
MOQ : 1 set
Delivery Time : 15 working days
Payment Terms : T/T in advance ,L/C
Supply Ability : 50 sets/ month
High Fidelity Protection Relay Testing / 51 Overcurrent Relay K3040
Relay protection test devices
1.Easy test
2.operation menu, Simple operation
3.Nominal input voltage:220VAC
4.Power:1000VA
1. Unique self-protection system assure the powerful protection when instrument is operating, automatic stop the output when the network is abnormal ;
2. Unique power switch and amplifier technology, so the output precision and power efficiency and factor are increased, which conforms to international tendency of energy save and environmental protection;
3. With alarm function of housing grounding testing and external voltage input, to guaranty personal security;
4. Two in one of meter and source, with function of both internal and external testing, self-calibration, oscillograph, and the duration of each oscillograph reaches 50S (optional function);
5. Offer independent Aux. DC to tested devices, 0 ~ 300V/0.6A (Poleless and adjustable);
6. Function of transducer and energy meter testing (optional function);
7. Testing interface offer unique output monitoring function and Pre-curve-tracing function, helps more on the spot analysis;
Technical Data of K3040
| Voltage generators | ||
| Setting Range | 4-phase AC (L-N) | 4 x 0 ... 130 V |
|
| 2-phase AC (L-L) | 2 x 0 ... 260 V |
| Power | 4-phase AC (L-N) | 4 x 70VA, at 0 ... 130 V |
|
| 2-phase AC (L-L) | 2 x 140VA, at 0 ...260 V |
| Accuracy | <0.07% reading + 0.03% range guaranteed at 0 ... 130 V <0.02% reading + 0.01% range typical at 0-130V | |
| Resolution | 1mV | |
| Current generators | ||
| Setting Range | 3-phase AC (L-N) | 3 x 0 ... 40 A |
|
| 1-phase AC (2L-N) | 1 x 0 ... 80 A |
|
| 1-phase AC (3L-N) | 1 x 0 ... 120 A |
| Power | 3-phase AC (L-N) | 3x 450VA , at 0 ... 40A |
|
| 1-phase AC (2L-N) | 1x 520VA, at 0 ... 80A |
|
| 1-phase AC (3L-N) | 1 x 1200 VA, at 0 ... 120A (Max.) |
| Accuracy | <0.07% reading + 0.06% range guaranteed at 0-40A <0.02% reading + 0.02% range typical at 0-40A | |
| Resolution | 1mA | |
| Generators, general | ||
| Frequency | Range | 0 ... 1000 Hz |
|
| Accuracy / drift | Error < 0.001Hz at 10 ... 65Hz, Error < 0.01Hz at 65Hz...450Hz Error < 0.02Hz at 450Hz...1000Hz |
|
| Resolution | 0.001Hz |
| Phase | Range | - 360° ... +360° |
|
| Accuracy / drift | Error < 0.2 ° |
|
| Resolution | 0.1° |
| Timer | Range | Infinite |
|
| Accuracy / drift | Error<0.1ms |
| DC generators | ||
| Voltage ranges | 0 ... 300V/180W | |
| Current ranges | 0 ... 20A/300W | |
| Accuracy | <0.07% reading + 0.03% range guaranteed at 0-300V <0.04% reading + 0.02% range typical at 0-300V | |
|
| <0.14% reading + 0.06% range guaranteed at 0-20A <0.05% reading + 0.02% range typical at 0-20A | |
| Resolution | 1mA; 1 mV | |
| Aux DC Supply | ||
| Range | 0...300V/0.6A | |
| Binary inputs | ||
| Number | 8 pairs | |
| Compatible Voltage | 10V ... 250V DC | |
| Binary outputs | ||
| Number | 4 Pairs | |
| Capacity | 250V/3A AC/DC | |
| Synchronization | ||
| Synchronization mode | GPS | |
| Harmonic | ||
| Harmonic overlap times | 2 ... 20 times | |
| Power supply | ||
| Nominal input voltage | 220V AC±20% | |
| Power | 1000VA | |
| Nominal frequency | 47Hz….65Hz | |
| Environmental conditions | ||
| Operation temperature | -5°C ... 55 °C | |
| Storage temperature | -20°C ... 75 °C | |
| Humidity range | 5% ... 90 %, non-condensing | |
| Weight | 20 KG | |
| Dimensions | 460(D)×140 (W)×360 (H) mm | |
| PC connection | RJ45 | |
K30 Series Protection Relay Test Set:
| Model | Channels | AC Outputs |
| K3063i / K3063Li | 10 output channels | 6*30A/3*40A/4*300V |
| K3030i / K3030Li | 7 output channels | 3*30A/4*300V |
| K3066 | 13 output channels | 6*20A/3*40A/7*130V |
| K3063 | 10 output channels | 6*20A/3*40A/4*130V |
| K3040 | 7 output channels | 3*40A/4*130V |
| K3030 | 7 output channels | 3*30A/4*130V |
Major functions:
| Items | IEEE(R) No. |
| Synchronization relay |
|
| Fault transplay |
|
| GPS Synchronization |
|
| Overcurrent relays | 50/76 |
| Inverse time overcurrent relays | 51 |
| Undercurrent relays | 37 |
| Ground fault relays | 50 |
| Directional overcurrent relays | 67 |
| Directional ground fault relays | 67N |
| Overvoltage relays | 59 |
| Undervoltage relays | 27 |
| Directional voltage relays | 91 |
| Directional power relays | 32 |
| Power factor relays | 55 |
| Differential protection (differential circuits) | 87 |
| Distance protection equipment (phase by phase) | 21 |
| Negative sequence overcurrent relays | 46N |
| Motor overload protection | 51/86 |
| Automatic reclosing devices | 79 |
| Tripping relays | 94 |
| Voltage regulating relays |
|
| Overimpedance relays, Z> |
|
| Underimpedance relays, Z |
|
| Time-delay relays |
|

|
|
High Fidelity Protection Relay Testing / 51 Overcurrent Relay K3040 Images |